DPG-2100 Controller

The DPG-2100 is a generator-set controller. It is used on generator sets from Barber-Colman, including the DPG-2100.

1
Generator sets
Barber-Colman
Brand

Generator sets using this controller

1
Barber-Colman DPG-2100

Troubleshooting

5

Symptoms & remedies

SymptomRemedy
Actuator lever goes to full fuel whenever the power is turned 'ON' and engine is not runningBroken actuator lead Check actuator Correct or replace actuator wiring. Replace controller because it should not cause actuator lever to go to full fuel with engine not running.
Engine hunts during operationLubricate or replace See installation information Readjust calibration
LED blinking fast but actuator does not move to open.Replace Controller if 95% of battery voltage is not present.
LED blinking slow and engine being cranked.Free Linkage. Check for damage to or improper adjustment of magnetic pickup. Replace or readjust.
System appears dead. No LED, fails to move actuator.If no voltage, check connections to battery. Correct wiring

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.