The DC2 generator set is a generator-set controller. It is used on generator sets from Kohler, including the RDC2 or DC2 generator set controller.
Also fitted to: Kohler 14/20RESA/RESAL, Kohler 20RESC/RESCL.
| Code | Meaning | Cause | Remedy |
|---|---|---|---|
| BusDeadLive | The bus is measured to be dead when one of the generators is supposed to be supplying voltage to the bus (closed contactor) | Bus metering V9A and V9B connections to V9 of paralleling protection harness are connected incorrectly. | |
| BusLiveDead | The bus is measured to be live when no generators are connected to it (both contactors open). | Bus metering V9A and V9B connections to V9 of paralleling protection harness are connected incorrectly. | |
| CfgModelNum | The two generators that are intended to be paralleled have incompatible model numbers. | Incorrect configuration of one of the generators. Different generator types. The paralleled generator sets must be the same kW model. (i.e. two 14 kW or two 20 kW models.) | |
| CfgSysVolt | The system voltage of the two generators intended to be paralleled is not the same. | One of the two generators is incorrectly configured. Intermittent connections on RBUS network wiring. | |
| Current A High Warning | Over Current Paralleled | Press AUTO or OFF * | |
| ErraticSig | The power metering on this controller gives a signal that is not consistent with the system configuration. Reversing the power direction does not resolve the problem. | Bad wiring to the CT. Too much tension on wires from the CT to the controller. | |
| Frequency High Warning | Over Frequency Paralleled | Press AUTO or OFF * | |
| Frequency Low Warning | Under Frequency Paralleled | Press AUTO or OFF * | |
| LossOfComAPM | The Automatic Paralleling Module has stopped communicating on RBUS. (An APM was detected on the RBUS network but is no longer communicating.) | APM is unplugged. Primary controller is powered down. Check the battery connections. See previous page for more information. Intermittent connections on RBUS network wiring. Check RBUS communication connections. | |
| LossOfComm2 | The primary controller has lost communication with the secondary controller. (A secondary controller was detected, then communication was lost.) | RBUS disconnected, secondary controller battery disconnected, updating firmware in secondary controller, or intermittent RBUS connections. | |
| LossOfField | This generator has absorbed more than 25% reactive power (magnetic excitation current) for 20 seconds Generator voltage on this generator is not calibrated correctly. Generator voltage on other generator is not calibrated correctly. Bus voltage on this generator is not calibrated correctly. Bus voltage on the other generator is not calibrated correctly. | ||
| MeterUnknown | This generator does not know if the metering is connected or the orientation of the connection. This means that the generators can’t share load accurately until this information is known. | System commissioning and startup not yet complete. See the APM instructions. | |
| MeteringOk | The generator has verified that the metering is connected correctly and that the direction is consistent with expected power direction. Status message indicates that the CT is connected to the generator correctly. | ||
| NoCurrent | The generator has applied load (using the other generator) and has observed no current on the power sensing inputs. | The CT is not connected to the controller. The output leads from the generator do not go through the CT in the correct direction. See the APM instructions. | |
| Reactive Power Low Warning | Loss of Field Paralleled | Press AUTO or OFF * | |
| Real Power High Warning | Over Power Paralleled | Press AUTO or OFF * | |
| Real Power Low Warning | Reverse Power Paralleled | Press AUTO or OFF * | |
| SyncFailure | The generator has been attempting to synchronize for over 2 minutes without success. | Generator is hunting. Advanced speed control settings need adjustment. Load is changing frequently to disturb the online generator. | |
| Voltage L1-L2 High Warning | Over Voltage Paralleled | Press AUTO or OFF * | |
| Voltage L1-L2 Low Warning | Under Voltage Paralleled | Press AUTO or OFF * |
| Symptom | Cause | Remedy |
|---|---|---|
| ATS Status or Configuration menus are not displayed on the RDC2 controller | Check the RBUS connections from the RDC2 controller on the generator to the interface board on the RXT transfer switch. | |
| ATS settings are not correctly configured | On systems equipped with the DC2 controller, a personal computer and Kohlerr SiteTecht software must be used to adjust the ATS settings. See Section 4.3. | |
| ATS status and settings are not correct | Check the ATS status and settings. Use the RDC2 controller menus and/or connect a personal computer (PC) to the RDC2 or DC2 controller on the generator set and use the Kohlerr SiteTecht program on your PC. | |
| Application code version number is outdated | Check the application code version number on the RDC2/DC2 controller. Check TechTools for the latest information about application code updates, and obtain the latest version if necessary. | |
| Battery acid on skin | Flush the affected area for 15 minutes with large quantities of clean water and seek medical aid if necessary. | |
| Battery acid splashes in the eyes | Immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid. | |
| Battery short circuits | Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (-) lead first when disconnecting the battery. Reconnect the negative (-) lead last when reconnecting the battery. | |
| Bodily injury and/or equipment damage | Battery short circuits | Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (--) lead first when disconnecting the battery. Reconnect the negative (--) lead last when reconnecting the battery. Never connect the negative (--) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together. |
| Corrosion, loose terminals, damaged wiring or connectors | Unplug connectors and check terminals and leads for corrosion. Remove corrosion from terminals and leads. Tighten loose terminals. Check wiring harnesses for continuity or short circuits. Recrimp or replace loosely connected lead terminals. | |
| Engine does not start | Low oil pressure or oil level | Check and refill oil if necessary. Refer to the 'Oil Check' section for details. |
| Engine overheats | Coolant level is low or coolant is contaminated | Check and refill coolant if necessary. Refer to the 'Cooling System' section for details. |
| Generator produces low voltage output | Dirty air filter | Clean the air filter as per the instructions in the 'Air Cleaner Service' section. |
| Loose or open connections or short circuits from the RXT interface board to the generator set | Check the connections from the RXT interface board to the generator set for loose or open connections or short circuits. | |
| Optional equipment such as Load Control Module (LCM) is not properly disconnected | Disconnect optional equipment such as the Load Control Module (LCM) and test the ATS operation to isolate problems to the transfer switch or connected accessories. | |
| RDC2 or DC2 controller on the generator set is not in AUTO mode, or engine starting battery is not connected and charged | Check that the RDC2 or DC2 controller on the generator set is in AUTO mode and that the engine starting battery is connected and charged. | |
| Source circuit breakers/switches to the transfer switch are not closed, or no power source is available | Verify that the source circuit breakers/switches to the transfer switch are closed and at least one power source is available. |