Home›Controllers›Allis-Chalmers 2800

Allis-Chalmers 2800 Controller

The Allis-Chalmers 2800 is a generator-set controller. It is used on generator sets from Cummins/Onan, including the DYJ Series.

1
Generator sets
Cummins/Onan
Brand
45–45 kW
Power range
Diesel
Fuel

Generator sets using this controller

1
Cummins/Onan DYJ Series

Troubleshooting

13

Symptoms & remedies

SymptomCauseRemedy
Fault lamp lights - no fault condition existsBe certain that no fault condition exists; Disconnect lead 29, 30 and 31 from TB11 inside control box (refer to wiring diagram); If fault lamp still lights with leads disconnected, remove and replace engine monitor plug-in printed circuit board
Fault lamp lights after engine is runningOil level - engine will shut down after approximately 12-1/2 seconds if low oil pressure sensor does not openCheck oil level
Fault lamp lights and engine stops cranking after approximately 75 secondsSee engine service manual for troubleshooting fuel system, ignition system, etc.; After correcting problem, reset the engine monitor by moving run-stop/reset-remote switch to reset position; Release and return to run position
Fault lamp lights immediately after engine startsOverspeed condition as engine startsCheck for overspeed condition as engine starts
High engine temperature fault lamp lights - no fault condition existsBe certain that no fault condition exists; Remove lead 31 from TB11 inside control box (refer to wiring diagram); If high engine temperature lamp still lights, remove and replace engine monitor plug-in printed circuit board
High engine temperature lamp lights after engine is runningDefective thermostat/thermostatsCheck thermostat/thermostats
High engine temperature lamp lights as soon as engine startsDefective sensor or actual high temperature conditionCheck for defective sensor or actual high temperature condition
Low oil pressure fault lamp lights - no fault condition existsBe certain that no fault condition exists; Disconnect lead 30 from TB11 inside control box (refer to wiring diagram); If low oil pressure lamp still lights, remove and replace engine monitor plug-in printed circuit board
Low oil pressure lamp lights after engine is runningOil level - engine will shut down after approximately 12-1/2 seconds if oil pressure is lowCheck oil level
Overcrank fault lamp lights after engine has run for approximately 75 secondsReplace start-disconnect circuit board
Overcrank fault lamp lights and engine stops cranking after approximately 75 secondsSee engine service manual for troubleshooting fuel system, ignition system, etc.; After correcting fault, reset monitor by moving run-stop/reset-remote switch to reset position, then to either run or remote to restart engine
Overspeed lamp lights - no fault condition existsReplace overspeed circuit board
When pressing test lamp button - one or more fault lamps do not light. Engine not running.Fault lamp/lamps burned outReplace

Fault codes and symptom→remedy steps extracted from this controller’s service/owner documentation; verify against the official manual before servicing. Aggregated from the service documentation of generator sets built on this controller.